Duct pressure drop calculator
Enter airflow, duct size, length and material and get velocity, friction rate and total pressure loss for one round or rectangular run. Add the fittings on that run as ΣK or an equivalent length, and the same page turns the result into fan power, annual energy and annual cost — then compares the sizes you are choosing between and says which one it would pick.
How to use this calculator
- Pick metric or imperial at the top — every field and every result follows.
- Choose round, square or rectangular, pick the material and enter the size and length.
- Enter the airflow, and the temperature and altitude if they differ from standard air.
- Add the fittings on this run as ΣK, as an equivalent length, or both.
- Set fan and drive efficiency, operating hours and your energy price to get the annual cost.
- Add the sizes you are choosing between and read the comparison, the recommended size and the payback.
What this calculates
One duct run — round, square or rectangular — from airflow, size, length and surface roughness to velocity and pressure loss, and from there to what that pressure loss costs over a year. It reuses the exact same Darcy-Weisbach + Colebrook-White engine already implemented and verified elsewhere on this site (against Moody-chart reference points: Re=1×10⁵, ε/D=1×10⁻⁴ → f=0.0180; Re=1×10⁶, ε/D=1×10⁻³ → f=0.0195, both matched to chart-reading precision) — the same calculation the duct network configurator runs for every straight section of a full branching system. This page is that one calculation on its own, with the fittings on that run and the money it costs, for when the question is about a single duct rather than a whole network.
Re = ρ·v·Dh / μ Reynolds number
1/√f = −2·log₁₀( (ε/Dh)/3.7 + 2.51/(Re·√f) ) Colebrook-White (implicit, solved iteratively)
Δp = f · (L/Dh) · (ρ·v²/2) Darcy-Weisbach
Dh = D round duct
Dh = 2ab/(a+b) = 4·Area/Perimeter rectangular duct
Colebrook-White has no closed-form solution — f appears on both sides — so it's solved by fixed-point iteration, seeded with the explicit Swamee-Jain approximation for a fast first guess. Below Re=2300 (laminar flow, unusual in real ductwork but included for completeness) the exact f=64/Re is used instead. Absolute roughness ε by material is the same published table (ASHRAE Fundamentals / Crane TP-410 / Idelchik) used throughout this site's duct tools, with galvanized steel set to ASHRAE's own 0.09 mm duct-friction-chart basis for spiral/longitudinal-seam duct.
Fittings, without a fitting database
On a short run, the elbows, tees and dampers often cost more than the duct itself, so a straight-duct number alone would be misleading. The published coefficients for every fitting geometry — ASHRAE's Duct Fitting Database — are a separate commercial product, and this page does not reproduce them. Instead it takes the local loss from whichever figure you already have, in either of the two forms engineers actually use:
Δp_local = ΣK · (ρv²/2) sum of loss coefficients × velocity pressure
Δp_local = L_equivalent · R equivalent length × friction rate
Entered together they add, because they are normally two different sets of fittings rather than two spellings of the same one. The readout keeps straight-duct loss and local losses on separate lines, and the breakdown chart shows the split, so it stays obvious when a bigger duct will not help — if three quarters of the loss is in the fittings, upsizing the duct barely moves the total.
What the duct costs to run
Pressure drop on its own does not tell a building owner anything. Multiplied by the flow it becomes air power; divided by the fan efficiency and the drive and motor efficiency it becomes the electrical power this one run draws from the wall; multiplied by operating hours and your energy price it becomes a yearly figure in your own currency.
P_air = Δp · Q air power, W
P_electrical = P_air / (η_fan · η_drive) wire power for this run, W
Cost = P_electrical / 1000 · hours · price per year
The page also reports the system constant k = Δp/Q². In turbulent flow the loss rises with roughly the square of the airflow, so that one number is the system curve for this run, and the chart draws it in full from zero to one and a half times your airflow — because the operating point is where that curve crosses a fan's characteristic, and that crossing lands wherever it lands. The link under the chart carries the duty straight into the fan operating point calculator, so you do not retype it.
Choosing a size
Add the sizes you are choosing between — ø315,
400x250, whatever you would write on a drawing — and each becomes a row
compared at the same airflow, length, material and fittings, so only the cross-section
changes. A coloured dot grades each velocity against normal practice rather than
passing or failing it: roughly 3 to 5 m/s for branch runs, 5 to 9 m/s for main ducts
and risers, below that oversized, above that industrial territory where noise and fan
energy start to bite, and red above 12 m/s where it stops being conventional HVAC
ductwork at all. Annual energy in kWh sits in the same table, because kilowatt-hours
compare the sizes whatever you pay per unit.
The cost calculation below it answers the other half. Duct cost is the sheet area — perimeter × length — at the price per square metre you enter. Energy is what the pressure drop of that run costs the fan over a year. Total adds the two over the evaluation period, and one row is tagged Best value: the lowest total.
That is a real optimum, not a preference. Sheet metal rises roughly with the perimeter, so with the duct diameter; fan energy falls with about its fifth power. The sum has a minimum somewhere in between, and where it sits depends on what you pay for each. Cheap duct and expensive electricity push it up a size or two; expensive duct, few operating hours or a short evaluation period push it back down. Change the duct price and watch the tag move — that is the tool doing its job, not a glitch.
One limit overrides the arithmetic: nothing above 12 m/s is ever tagged, however cheap it comes out, because noise is not a line in this calculation and a duct at 20 m/s is unbuildable in a building whatever the spreadsheet says. When a cheaper row is skipped for that reason the note says so and names it. Leave the duct price at 0 and the tag falls back to the engineering rule instead: the smallest size still under 9 m/s and 1 Pa/m, the usual commercial-ventilation design ceilings — conventions, not a code requirement.
Payback is the same comparison read the other way: how much extra sheet a larger size needs against the energy it saves each year. All of it counts sheet area only — fittings, insulation, hangers and labour are not in it — so treat the money as a screening number rather than a quotation.
When to use the other duct tools instead
This page only answers the forward question — given this duct, what happens. Two related tools on this site solve different problems with the same underlying physics: the duct sizing calculator solves it in reverse (given a target velocity or friction rate, what size duct do I need), and the duct network configurator extends this same duct calculation across a full branching system with transitions, elbows, tees, dampers and louvers, balancing flow across parallel paths. Reach for those when the question is "what size" or "what does the whole system add up to" rather than "what does this one duct do".
Frequently asked questions
How do I calculate pressure drop in a duct?
Pressure drop in a straight duct is Darcy-Weisbach: Δp = f · (L/Dh) · (ρv²/2). You need the velocity, which comes from airflow divided by cross-section area, the hydraulic diameter, the air density and the Darcy friction factor, which depends on the Reynolds number and the relative roughness of the duct surface. This page does all of that from airflow, size, length and material, and adds the fittings on top if you tell it how many.
Does this include elbows, bends and other fittings?
Yes, but you supply their resistance. There is no built-in commercial fitting database here, so the page takes local losses two ways: as a sum of loss coefficients, ΣK, which it multiplies by the velocity pressure, or as an equivalent length of straight duct, which it multiplies by the friction rate. Both can be used at once, because they are usually two different sets of fittings rather than two ways of writing the same one. The result is split into straight-duct loss and local losses so you can see which is which.
What is a good air velocity in a duct?
As a rule of thumb for commercial ventilation, 3 to 5 m/s is normal in branch and terminal runs where outlet noise matters, and 5 to 9 m/s in main ducts and risers. Below about 2.5 m/s the duct is larger and more expensive than the duty needs; above about 9 m/s you start paying for it in noise and fan energy, which is common and accepted in industrial systems. These are design conventions, not code limits, and the calculator labels your velocity against them rather than passing or failing it.
What friction rate should I design to?
Around 0.8 to 1.2 Pa/m, or roughly 0.08 to 0.1 in. wg per 100 ft, is the usual target for commercial ventilation using the constant-friction method. It is a convention rather than a limit: it exists because it happens to land near the economic optimum for typical duct prices and electricity prices. This page works that optimum out directly instead, from your own duct price, operating hours and energy price — so when those differ from the typical case, the answer moves off the rule of thumb, which is the point.
How does the calculator work out the annual running cost?
Air power is the total pressure loss multiplied by the volume flow. Dividing it by the fan efficiency and the drive and motor efficiency gives the electrical input power that this one duct run costs the fan. Multiplied by your operating hours and your energy price, that becomes an annual figure. It is the cost of the pressure drop you are looking at, not of the whole system.
Is a bigger duct worth the money?
That is exactly what the cost calculation decides. Enter a duct price per square metre of surface and an evaluation period, and every size gets a duct cost, an annual energy cost and a total of the two over that period. The lowest total is tagged Best value. Because sheet metal grows roughly with the diameter while fan energy falls with about its fifth power, that total has a genuine minimum — cheap duct pushes it to a larger size, expensive duct to a smaller one. It covers sheet area only, so fittings, insulation, hangers and labour are not in it; treat it as the first screening number, not a quotation.
Why is a row with a lower total not the recommended one?
Because nothing above 12 m/s is ever tagged, however cheap it comes out. Noise and regenerated pressure loss at fittings are not lines in this calculation, and at those velocities they dominate the decision, so a purely economic answer there would be wrong. When a cheaper row is skipped for that reason the note under the table says so and names the size, rather than leaving you to wonder.
What evaluation period should I use?
The default is 15 years, which is a common horizon for building services life-cycle costing and well inside the service life of sheet metal ductwork. Shorten it and capital cost dominates, so the optimum moves to a smaller duct; lengthen it and energy dominates, so it moves to a larger one. The figure is a straight sum of undiscounted costs — no discount rate, no energy price escalation — because both are project-specific assumptions this page has no business guessing.
Does duct material make a real difference?
Less than most people expect at normal velocities, and the material bar chart on the page shows it directly. Absolute roughness runs from about 0.03 mm for PVC and aluminium to 0.09 mm for galvanized steel and 3 mm for concrete, but friction factor depends on roughness only logarithmically, so swapping galvanized steel for plastic typically moves the pressure drop by single-digit percent. Flexible duct is the exception — even fully extended, it is in a different class.
Round or rectangular — which has less pressure drop?
Round wins at equal cross-section area, because a circle has the smallest perimeter for a given area and therefore the largest hydraulic diameter. The gap grows with aspect ratio: a 400×250 duct behaves far better than an 800×125 one of the same area. Enter both shapes in the size comparison and you can read the difference off the same table.
What is the system constant k for?
In turbulent flow the pressure loss rises with roughly the square of the airflow, so one number describes the whole system curve: k = Δp/Q². The chart plots that curve from zero to one and a half times your airflow, because the operating point is where it crosses the fan characteristic and that crossing is not necessarily near the flow you entered. The link under the chart carries the duty across. Find the operating point against a fan curve →
Does altitude or temperature change the result?
Yes, through air density. Hot air and high altitude are both thinner, so the same volume flow produces less velocity pressure and less pressure drop — but the fan also produces less pressure, which is why selections have to be made at the actual density. Density here comes from the same barometric and moist-air engine used by the air density calculator.