Cooling load calculator

Sensible and latent cooling load, hour by hour, from a real solar-position calculation — per facade, with sol-air temperature on walls and roof. Space load and SHR, required supply airflow, and the cooling coil duty including outdoor air, heat recovery and fan heat.

Sensible + latent + SHR Peak hour found, not assumed Space load and coil load Free, no sign-up
Room cross-section with cooling load sources by source

Room data

Inputs only — every result is on the right.

Room and design conditions

Envelope

Facades and glazing

Every facade in the calculation, one entry per orientation:

Internal gains

Air and system

Annual energy and cost

Cooling coil load
—
Space load
—
Space sensible
—
Space latent
—
Space SHR
—
Supply airflow
—
Peak
—
Annual cooling cost
—
Waiting for input
—

Cooling coil duty at the worst hour of the season.

Space cooling load
—
Space SHR
—
Cooling coil load
—
Coil SHR
—
Required supply airflow
—
Supply air changes
—
Mixed air on the coil
—
Outdoor humidity ratio
—
Indoor humidity ratio
—
Sun at the peak hour
—
Volume
—
Net wall area
—
Glazing area
—
Annual — envelope and air
—
Annual — solar
—
Annual — internal gains
—
Annual — latent
—
Annual cooling energy
—
Annual electricity
—
Annual cooling cost
—

Link copied — it reopens with these exact inputs.

How to use this calculator

  1. Search your location. It fills the summer design temperature, humidity, mean daily range, latitude and degree days in one go — latitude is what the sun model needs.
  2. Enter the room, then pick constructions or type your own U-values.
  3. Build the facades: one entry per orientation with its wall area, glazing and shading. “Fill from room dimensions” does a rectangular room in one click.
  4. Set the people, lights and equipment, the fresh air, and the supply air temperature.
  5. Read the space load and its SHR, the supply airflow it needs, and the coil duty — at the worst hour the model found, with the whole day plotted underneath.

What this calculates

A cooling load is not one number. It is a sensible part and a latent part, it changes hour by hour, and the load on the room is not the load on the cooling coil. This tool keeps those three distinctions separate instead of collapsing them:

Space sensible = Σ U·A·(t_sol-air − t_i) + Σ A_glass·g·F_shade·E_t + people_sens + lights + equipment_sens + 0.34·V_infiltration·(t_o − t_i) Space latent = people_lat + equipment_lat + 0.834·V_infiltration·(x_o − x_i) SHR = sensible / (sensible + latent) Supply air = Space sensible / (0.34 · (t_i − t_supply)) Coil load = Space load + 0.34·V_fresh·(t_o − t_i)·(1 − η_sens) + 0.834·V_fresh·(x_o − x_i)·(1 − η_lat) + fan heat + duct gain x = humidity ratio, g/kg dry air E_t = total solar irradiance on that surface, W/m² 0.34 W/(m³/h·K) = air sensible heat capacity 0.834 W/(m³/h·(g/kg)) = air latent heat capacity

The sun is calculated, not looked up

Most quick cooling calculators carry a small table of “peak irradiance by orientation” — one watt-per-square-metre figure per compass point, usually with west marked as the worst case. That table cannot tell you when the peak happens, and it is wrong for any latitude but the one it was written for.

This tool computes the solar position instead: declination from the day of the year, hour angle from the time, then solar altitude and azimuth from the latitude. The angle of incidence on each facade follows, and the ASHRAE clear-sky model turns it into direct, diffuse and ground-reflected radiation — with the standard correction for diffuse radiation on vertical surfaces, which is not isotropic.

δ = 23.45 sin(360 (284 + n) / 365) declination H = 15 (h − 12) hour angle sinβ = cos L cosδ cos H + sin L sinδ solar altitude E_DN = A / exp(B / sinβ) direct normal, clear sky cosθ = cosβ cos(φ − ψ) sinΣ + sinβ cosΣ angle of incidence E_t = E_DN cosθ + diffuse + ground-reflected

The consequence is worth stating plainly: with all other inputs fixed, east glazing in Kraków peaks around 08:00, west glazing around 16:00, and south glazing at noon in August rather than June — the sun is lower by August, so it strikes south glass closer to straight on and delivers more through it, not less. A fixed table shows none of that. Leave the design month and hour on “Auto” and the tool searches every hour of the three months around the solstice and reports the one that governs.

Sol-air temperature: why roof colour matters

An opaque surface in sunshine does not conduct towards the air temperature. It conducts towards the sol-air temperature — the air temperature plus the absorbed solar radiation divided by the outside surface film coefficient, less a correction for long-wave radiation to the sky on roofs:

t_sol-air = t_o + (α / h_o) · E_t − ΔR / h_o α / h_o = 0.021 (white) … 0.052 (dark) m²·K/W ΔR / h_o = 3.9 K for a roof, 0 for a vertical wall

In the default case that puts a medium-coloured roof at about 54 °C of effective driving temperature while the air is 30 °C. Switching the surface colour from white to dark moves the whole coil duty by more than a kilowatt and can move the peak into a different month. For an industrial hall with a large dark roof, this term is often the single biggest thing a simple U·A·ΔT calculation misses.

Humidity, and where the latent load really sits

Indoor and outdoor air are entered as temperature plus relative humidity, and both go through the same psychrometric engine that draws the Mollier h-x chart — so a state computed here means exactly what it means there. People, equipment, infiltration and fresh air all report both parts, and the results show the sensible heat ratio twice, because the two numbers answer different questions.

The space SHR is what the room needs and what sets the supply air condition. The coil SHR is what the coil has to deliver, and it is always lower, because the outdoor air brought in for ventilation carries most of the moisture. On the default office the room sits near 0.93 while the coil sits well below it — size a coil from the room figure alone and it will meet the temperature and lose the humidity.

Space load is not coil load

The space load is the heat to be removed from the room. The coil load adds everything the air-handling side contributes: the outdoor air after whatever the heat recovery takes out of it, the supply fan’s own power turning into heat in the air stream, and the gain the ducts pick up on the way. The tool also computes the mixed-air state entering the coil from the return and fresh streams, which is exactly what a coil selection needs — so the result links straight into the coil designer with the duty, airflow, entering temperature and entering humidity already filled in.

Annual energy, with each term on its own road

An earlier version of this page took the whole design-point load, divided it by the design temperature difference to make a watts-per-kelvin figure, and multiplied that by cooling degree days. That is the right method for conduction and ventilation, and the wrong method for everything else: people, lights, equipment and sunshine are not proportional to the indoor–outdoor temperature difference, so turning them into W/K and scaling them by degree days models something that does not exist.

Each term now travels its own road, and each appears as its own line in the results:

Envelope + infiltration (sensible) = UA × CDD × 24 / 1000 [kWh/yr] Mechanical ventilation (sens.) = UA_vent × CDD × run hours / 1000 Internal gains = gains × season days × run hours / 1000 Solar, glazing and opaque = sky model integrated over run hours and season months × clear-sky fraction Latent = latent × season days × run hours × seasonal latent factor

Envelope conduction and infiltration run over the full 24 hours a degree day describes, because a building keeps gaining heat while the plant is off and that heat still has to be removed. Mechanical ventilation only runs when the system runs, so its share is scaled by the operating window. The solar term is integrated from the same sky model that produced the design figure, over the operating hours of the cooling-season months, then reduced by a clear-sky fraction — because the model is a clear sky and real seasons are not. It covers both the radiation that comes through the glazing and the sol-air uplift on the opaque walls and roof, which degree days cannot carry because they are built on air temperature alone. That is why changing the external surface colour moves the annual figure as well as the design point — on the default office, white to dark is about 9% of the yearly cooling bill.

What this still does not do

Thermal mass. A gain becomes a load in the hour it occurs, with no time lag and no damping by the structure. That is the line between this tool and the ASHRAE Radiant Time Series or Heat Balance methods, which distribute the radiant share of each gain over the following hours through coefficients that depend on the construction. For a heavy building the real peak is lower and later than the one shown here, so read this as a sizing estimate on the safe side rather than a dynamic simulation.

Frequently asked questions

Does this calculate the latent (humidity) load as well as the sensible load?

Yes. Indoor and outdoor air are entered as dry-bulb temperature plus relative humidity, and both states go through the same psychrometric engine that drives the Mollier h-x calculator. Every air stream — people, equipment, mechanical ventilation and infiltration — reports a sensible and a latent part, and the results show the sensible heat ratio for the room and for the coil separately.

What is the difference between the space load and the cooling coil load?

The space load is the heat that has to be taken out of the room: envelope, solar, internal gains and infiltration. The coil load is what the cooling coil has to do, which also includes the outdoor air brought in by mechanical ventilation (after any heat recovery), the supply fan’s own heat and heat picked up in the ducts. On a space with a lot of fresh air the coil load can be half again the space load, which is why sizing a coil from the room figure alone undersizes it.

Where does the solar gain figure come from?

From a solar-position calculation, not a lookup table. The tool computes solar declination, hour angle, solar altitude and azimuth for the latitude, month and hour, then the angle of incidence on each facade, and feeds them into the ASHRAE clear-sky model for direct, diffuse and ground-reflected radiation. That is why east glazing peaks in the morning and west glazing in the late afternoon, in different months, instead of sharing one “worst case” number.

What does "Auto — worst hour" actually search?

Every hour of the three months around the summer solstice — all twelve in the tropics — and it reports the hour with the highest coil load. The window is three months rather than the whole season because the design dry bulb you enter is applied unchanged in every month searched, and a September sun angle paired with a July temperature is not a real condition. Within that window the worst hour is a result, not an assumption. Any month and hour can still be pinned by hand if you need to match someone else’s calculation.

Why does the roof colour change the answer so much?

Because an opaque surface in sunshine does not conduct heat towards the air temperature, it conducts towards the sol-air temperature: the air temperature plus the absorbed solar radiation divided by the outside surface film coefficient. A dark roof in full sun can sit 25 K above the air around it, so U × A × ΔT against air temperature can understate the roof gain several times over. The same sol-air calculation runs on every facade.

How do I enter glazing on more than one facade?

Add one entry per facade: pick the orientation, type the wall and glazing area and the shading, and press Add. Each entry becomes a chip you can remove. “Fill from room dimensions” generates the walls for a rectangular room from the length, width, height and which way the main facade faces, so the common case takes one click. A horizontal entry is a skylight and is cut out of the roof area.

What is the required supply airflow based on?

The space sensible load divided by the air’s heat capacity and the difference between the room setpoint and the supply air temperature: V = Qsensible / (0.34 × (troom − tsupply)). If that comes out below the fresh-air requirement, the fresh-air figure is used instead. The result is also shown per square metre and as air changes, and it is what the fan heat is calculated from.

Is the annual energy estimate still a degree-day calculation?

Only for the part of the load that degree days actually describe. Envelope conduction and the sensible part of ventilation and infiltration scale with the indoor–outdoor temperature difference, so they go through cooling degree days. Internal gains do not, so they are integrated over the operating hours you enter. Solar is integrated from the same sky model over the operating hours of the cooling-season months, reduced by a clear-sky fraction. Latent load runs over operating hours with a seasonal factor. Each term appears as its own line in the results.

What does this calculator not do?

Thermal mass. Gains become load in the hour they occur, with no time lag and no damping by the structure — that is the difference between this and the ASHRAE Radiant Time Series or Heat Balance methods. For a heavy building the real peak is lower and later than the one shown here, so treat this as a sizing estimate on the safe side rather than a dynamic simulation. Ground floors also conduct towards the outdoor air temperature here, which overstates a slab on grade.

Can I carry the result into a coil selection?

Yes. The tool computes the mixed-air state entering the coil from the return and fresh-air streams, and links straight into the coil designer with the duty, airflow, entering temperature and entering humidity already filled in. The same air states open in the psychrometric calculator if you want to see the process on an h-x chart.

Which U-values does it use?

The same construction tables as the heat loss calculator — one table serving both tools, so a wall picked here means exactly the same U-value it would in the heating calculation. Every element also accepts a custom U-value if you have a calculated one, for instance from the U-value calculator.

Is it free, and are my inputs stored anywhere?

Free, with no sign-up. Everything runs in your browser; inputs stay on your device and the shareable link encodes them in the URL so a colleague opens the same case.

Solar radiation comes from the ASHRAE clear-sky model with monthly A/B/C coefficients and a standard solar-position calculation — a clear-sky design-day figure for the latitude you enter, not measured irradiance, and with no allowance for terrain, nearby buildings or local turbidity. Sol-air temperature uses typical absorptance-to-film-coefficient ratios by surface colour. Solar transmission through glazing uses the normal-incidence g-value with a shading multiplier; the angular dependence of g and the separate treatment of direct and diffuse transmission are not modelled. No thermal mass, no time lag, no radiant/convective split — gains become load in the hour they occur, so the peak is on the safe side of a dynamic calculation. The ground floor conducts towards the outdoor air temperature here, which overstates a slab on grade, where the ground sits near the annual mean; set the floor to “Internal” if you would rather leave it out. The U-value, g-value, occupant-gain, shading and COP/EER presets are typical/representative values for screening, not certified figures for any specific product or assembly. Summer design conditions, degree days, daily range and latitude from the reference-location table are single-city, order-of-magnitude starting points — always replace them with your own local design data. The default electricity price is a round placeholder, not live market data. The annual figures are an engineering estimate with no part-load, free-cooling or occupancy-schedule modelling — not a metered-bill prediction. Provided for engineering guidance; verify against a full calculation for a real design.