Psychrometric calculator & Mollier h-x diagram
Calculate moist-air properties and HVAC processes on an interactive Mollier h-x psychrometric chart. Add air states, heating, cooling, humidification and mixing, and get humidity ratio, enthalpy, dew point, wet-bulb temperature, specific volume and density at every point — plus the load of every process between them (Δt, Δx, Δh and sensible, latent and total heat).
Alt+click the chart to add a state point there · Ctrl+click (⌘+click on Mac) to remove the nearest point.
What is a psychrometric calculator?
A psychrometric calculator determines the thermodynamic properties of moist air from two known conditions — typically dry-bulb temperature and relative humidity. From that pair it derives humidity ratio, enthalpy, dew point, wet-bulb temperature, vapour pressure, specific volume and density, all at the barometric pressure of the site. This one goes a step further: it also calculates the HVAC processes between air states, so a whole air handling unit can be modelled in one place rather than point by point.
How to use this calculator
- Set the altitude, or type the sea-level pressure directly. Both feed one barometric pressure used by every point on the page.
- Set the system airflow. Plain state points do not need it, but every capacity in kW and every kg/h of water comes from it — and a mixing row divides it between the two streams, so there it changes the result itself.
- Add the first air state: dry-bulb temperature and relative humidity.
- Add a process — heating, cooling, humidification or mixing. Each one starts from a point you already have and asks only for what that process actually needs.
- Read the row: every point shows t, x, h, RH, dew point and wet-bulb inline, and the two tables below give the full state of each point and the balance of each process.
- Drag a row by its number to reorder the chain. Alt+click the chart adds a state point where you clicked; Ctrl+click removes the nearest one.
HVAC psychrometric processes
A row is either an air state you type in, or one of the standard psychrometric processes — mixing, heating, cooling with dehumidification, humidification — that takes an existing point and changes it. Processes carry the airflow of the point they start from, so a chain of them behaves like one air handling unit: outdoor air, mixing, coil, humidifier, supply. Only those declared relations are drawn on the chart — a state point you add for comparison stays a point and is not joined to anything.
Air state
Parameters: dry-bulb temperature and relative humidity. Everything else — humidity ratio, enthalpy, dew point, wet-bulb, vapour pressure, specific volume and density — follows from those two plus the barometric pressure. This is the row you use for outdoor air, room air or any measured condition.
Heating
Parameters: source point, and either the temperature the air leaves with or the rise Δt. A heating coil adds no water, so the humidity ratio x carries over unchanged and the process runs straight up the constant-x line — vertically on an h-x chart, where the horizontal lines are the isotherms. Relative humidity falls as the air warms — same moisture, higher saturation pressure — and the dew point does not move at all. The capacity is mass flow of dry air times the enthalpy rise. Asking for a temperature below the entering dew point is refused, because a dry coil cannot get there without condensing: that is a cooling row.
Cooling and dehumidification
Parameters: source point, one temperature and the bypass factor — and you choose which temperature you are giving. As long as the coil surface stays above the entering dew point nothing condenses, the process runs vertically down the constant-x line and SHR = 1. Once the surface is colder than the dew point, the air that touches the fins leaves saturated at that surface temperature, the rest slips past untreated, and the two mix on the way out. The bypass factor is that untreated share; zero would mean a coil of infinite surface, and real coils sit between 0.05 and 0.20.
Because of that mixing the coil surface and the supply air are two different temperatures, so the row lets you pick which one you are specifying. Leaving air is the usual case: you give the supply temperature and the apparatus dew point is solved backwards from t₂ = ADP + (t₁ − ADP)·BF. Coil surface (ADP) works the other way: you give the surface temperature and read what the air leaves with — air entering at 30 °C and 30 % RH, cooled on an 8 °C surface with 10 % bypass, supplies 10.2 °C at 88 % RH, not 8 °C and 100 %. Δt is the third way in: you give the drop and the rest is solved as in Leaving air.
Note what the bypass factor does not do: on a dry coil there is no wetted surface, so the air leaves exactly at the temperature you asked for and the bypass field changes nothing. The ADP, BF and CF columns then simply report where the constant-x line would meet saturation — which is the entering dew point.
Humidification
Parameters: source point, humidifier type and target relative humidity. Steam injection adds vapour that is already hot, so the air gains moisture at nearly constant temperature — in fact it warms by a few tenths of a degree. An evaporative (water) humidifier takes the heat of evaporation out of the air itself, so the process runs along a line of constant enthalpy and the air cools as it moistens: adiabatic humidification, the same physics as a wet-bulb thermometer. The moisture gain needed to reach the target humidity is solved by iteration, because both routes reach a given RH at a different humidity ratio.
Mixing
Parameters: the two points being mixed and the airflow of stream A. Stream B takes the rest of the system airflow, so the two always add up to what the fan actually moves. Mixing is a mass balance, not a volume balance: each stream is converted to kilograms of dry air per hour using its own density, which is why 2 000 m³/h of cold outdoor air and 8 000 m³/h of warm return air mix as 21 % / 79 % rather than 20 % / 80 %. The mixed point lands on the straight line between the two states, at the position given by those mass shares.
Difference between two points
Parameters: two points. Not a process at all — a comparison. It reports Δt, Δx, Δh, the process ratio ε and, with an airflow, the sensible, latent and total load between two measured or calculated states. Useful for checking a coil from a datasheet, or an existing installation against the design.
Psychrometric calculator for AHU processes
Use the chart to model outdoor air, return air, mixed air, heating, cooling, dehumidification and humidification in an air handling unit. Each process starts from a point you already have and carries the airflow onward, so a winter unit reads as outdoor air + return air → mixing → heating → humidification → supply, and a summer unit as outdoor air + return air → mixing → cooling and dehumidification → reheat → supply. The chart then shows the whole path the air takes through the unit, and the tables give the entering and leaving state of every component together with its sensible, latent and total load — the numbers a coil, humidifier or heat recovery selection needs.
Cooling coil analysis
Every cooling step in the table is analysed the way a coil selection is: total, sensible and latent capacity, the sensible heat ratio, the condensate rate, and the three numbers that describe the coil surface itself.
ADP the apparatus dew point — extend the process line until it
meets the saturation curve; that is the coil surface temperature
BF = (t₂ − ADP) / (t₁ − ADP) bypass factor, the share of air that misses the fins
CF = 1 − BF contact factor
SHR = Qₛ / Qₜ sensible heat ratio
Sensible capacity is computed with the full specific heat of moist air, 1.006 + 1.86·x, so sensible and latent add up exactly to the total. The common shortcut Qₛ = m·1.006·Δt loses about two per cent and leaves the three numbers not adding up.
What the Mollier diagram shows
The Mollier h-x chart plots every state of humid air on two axes — enthalpy (h) and humidity ratio (x) — with dry-bulb temperature, relative humidity, wet-bulb temperature and dew point all readable as curves and lines across the same chart. It's the standard way to size cooling coils, humidifiers and mixing processes in central air handling units. This calculator gives you the same seven numbers a chart reading would, computed directly.
Mollier diagram vs psychrometric chart
A Mollier h-x diagram and a psychrometric chart describe the same moist-air thermodynamic relationships using different axis conventions. The psychrometric chart, common in the United States, puts dry-bulb temperature on the horizontal axis and humidity ratio on the vertical one. The Mollier h-x chart, standard in European HVAC engineering, swaps them and shears the coordinate system along the enthalpy lines, which is why its isotherms fan out instead of running level. Every quantity — enthalpy, humidity ratio, relative humidity, dew point, wet bulb, specific volume — is identical on both; only the geometry differs. CloudAir draws the Mollier h-x representation, and this page uses both names because engineers do.
Humidity ratio and enthalpy
Psat(t) ASHRAE saturation pressure, Pa
TWO branches: over ice below 0 °C, over water above
Pv = RH/100 · Psat(t)
x = 0.621945 · Pv / (P − Pv) humidity ratio, kg water / kg dry air
h = 1.006·t + x·(2501 + 1.86·t) enthalpy, kJ/kg dry air
The ice branch matters more than it looks. A single over-water fit carried below zero overstates the humidity ratio of −10 °C air at 90 % RH by about 10 %, and the saturation pressure at −20 °C by over 20 % — which is exactly the range that decides a heat recovery or a winter humidification duty.
x is the mass of water vapour carried per kilogram of dry air — the number that determines how much moisture a coil needs to remove, or a humidifier needs to add. Enthalpy is the total heat content of that moist air, dry air plus its water vapour, and is what actually sizes a cooling or heating coil.
Dew point and wet-bulb temperature
Dew point is the temperature at which the air's vapour pressure would equal the saturation pressure — where condensation starts on a cold surface. It is found by inverting the same saturation curve the chart draws, so a point's dew point always lands exactly on the RH = 100 % line rather than a degree or two beside it.
Wet-bulb temperature is solved from the adiabatic saturation balance, not from a psychrometer coefficient: the air is brought to saturation by evaporating water into it, with the water entering at the wet-bulb temperature itself. That is the definition the chart's constant wet-bulb lines follow, and for an evaporative humidifier it is also the lowest temperature the air can reach.
Frequently asked questions
What is a psychrometric calculator?
It is a tool that derives the full thermodynamic state of moist air from two known properties. Give it dry-bulb temperature and relative humidity and it returns humidity ratio, enthalpy, dew point, wet-bulb temperature, vapour pressure, specific volume and density at the barometric pressure you set.
What is a Mollier h-x diagram?
A chart of moist air with enthalpy (h) and humidity ratio (x) as its coordinates, drawn with the isotherms fanning out from a sheared axis so that lines of constant enthalpy run straight. Richard Mollier introduced it in 1923, and it remains the standard way of presenting humid-air processes in European HVAC engineering.
What is the difference between a Mollier diagram and a psychrometric chart?
Only the axis convention. A psychrometric chart plots dry-bulb temperature horizontally and humidity ratio vertically; a Mollier h-x chart swaps the two and shears the grid along the enthalpy lines. The physics, the curves and every number read from them are the same, which is why the same calculation answers both.
How do you calculate humidity ratio?
From the vapour pressure and the barometric pressure: x = 0.621945 · Pv / (P − Pv), in kilograms of water per kilogram of dry air. The vapour pressure itself is relative humidity times the saturation pressure at that temperature, and the saturation pressure follows the ASHRAE equation — over ice below 0 °C, over water above it.
How do you calculate moist-air enthalpy?
h = 1.006·t + x·(2501 + 1.86·t), in kJ per kilogram of dry air, counted from 0 °C. The first term is the dry air, the second the water vapour it carries: the latent heat of that water plus its own sensible heat. Coil and heater capacities come from the change in this number times the mass flow of dry air.
How is a psychrometric chart used in AHU design?
Each component of the unit is a process on the chart. Outdoor and return air mix into one state, the heating coil moves it along a line of constant humidity ratio, the cooling coil drops it towards the saturation curve and condenses water out, the humidifier moves it back up. Reading the entering and leaving state of each one gives the sensible, latent and total load that sizes it — and the whole path shows at a glance whether the supply air lands where the room needs it.
The air density in the table is humid-air density, ready to hand to the fan laws calculator as ρ₂/ρ₁ — humid air is measurably less dense than dry air at the same temperature and pressure. At sea level it matches the air density calculator to four decimals; at altitude the two drift apart by a few tenths of a per cent, because that page uses an exponential barometric formula and this one the ISA standard atmosphere.