Ecodesign compliance checker — air heaters, heat pumps, chillers, air conditioners & process chillers

Check an air heater, air-to-air heat pump, chiller, air conditioner or high-temperature process chiller against the minimum efficiency and NOx thresholds of Regulation (EU) 2016/2281. Enter the values your manufacturer already declares on the product's technical documentation and get a straight pass/fail against both the 2018 and the current 2021 tier.

2021 tier currently in force EU 2016/2281 Free, no sign-up

Product data

Use the values already declared on the manufacturer's technical documentation — this checks them against the regulation, it does not derive them from scratch.

kW
%

Don't have a rated heat output yet? Size the heater first from your airflow and required temperature rise, then come back and check it here.

Result — 2021 tier
Declared value
2021 minimum
Margin
Waiting for input

Checked against the tier currently in force.

Category
Efficiency — Tier 1 (from 2018-01-01)
Efficiency — Tier 2 (from 2021-01-01)
NOx — Tier 1
NOx — Tier 2
Basis

Link copied — it reopens with these exact inputs.

How to use this checker

  1. Pick the device type — air heater, air-to-air heat pump, chiller/AC, high-temperature process chiller, or fan coil unit. Each has its own table in the regulation.
  2. Pick the subtype that matches your product — fuel, drive type, heat rejection method — since the threshold depends on it.
  3. Enter the values already on the product's technical documentation: rated output, declared seasonal efficiency (ηs,h / ηs,c / SEPR) and, where applicable, declared NOx.
  4. Read the verdict against the 2021 tier, which is the one currently in force, plus the 2018 figure for reference.

What this checker does — and doesn't — do

Regulation (EU) 2016/2281 sets minimum thresholds directly in its own text (Annex II), but it delegates the detailed measurement and calculation methodology to separate harmonised standards that aren't publicly available. This tool doesn't try to reconstruct that methodology from first principles. Instead it takes the efficiency and NOx figures a manufacturer is already legally required to declare — on the rating plate, in the technical documentation, and on their website — and checks them directly against the regulation's own published tables. It's a compliance screen, not a substitute for the manufacturer's own conformity assessment.

Air heaters — minimum ηs,h

CategoryTier 1 (2018)Tier 2 (2021)
Gas/liquid air heater, standard72%78%
B1 < 10 kW or C2/C4 < 15 kW68%78% (exception removed)
Electric air heater30%31%
Air-to-air heat pump, electric, excl. rooftop133%137%
Rooftop heat pump115%125%
Air-to-air heat pump, ICE-driven120%130%

The small-unit exception disappears in 2021. Table 1 gave B1 air heaters under 10 kW and C2/C4 air heaters under 15 kW a lower 68% bar in 2018. Table 2 removes that row entirely — from 2021 every non-electric air heater, regardless of size, has to reach 78%. A heater that legitimately passed in 2018 at 70% is non-compliant today.

Chillers and air conditioners — minimum ηs,c

CategoryTier 1 (2018)Tier 2 (2021)
Air-to-water chiller, electric, < 400 kW149%161%
Air-to-water chiller, electric, ≥ 400 kW161%179%
Water/brine-to-water chiller, electric, < 400 kW196%200%
Water/brine-to-water chiller, electric, 400–1500 kW227%252%
Water/brine-to-water chiller, electric, ≥ 1500 kW245%272%
Air-to-water chiller, ICE-driven144%154% (≥400 kW only)
Air-to-air AC, electric, excl. rooftop181%189%
Rooftop air conditioner117%138%
Air-to-air AC, ICE-driven157%167%

High-temperature process chillers — minimum SEPR

Heat rejectionCapacityTier 1 (2018)Tier 2 (2021)
Air< 400 kW4.55.0
Air≥ 400 kW5.05.5
Water< 400 kW6.57.0
Water400–1500 kW7.58.0
Water≥ 1500 kW8.08.5

NOx limits

Air heater NOx tightens in 2021; heat pump, chiller and AC NOx (for internal-combustion-engine-driven units) is set once, from 26 September 2018, with no later revision in this regulation.

CategoryTier 1Tier 2
Air heater, gas-fired100 mg/kWh (from 2018-09-26)70 mg/kWh (from 2021-01-01)
Air heater, liquid-fired180 mg/kWh150 mg/kWh
Heat pump/chiller/AC, external combustion, gas70 mg/kWh
Heat pump/chiller/AC, external combustion, liquid120 mg/kWh
Heat pump/chiller/AC, internal combustion, gas240 mg/kWh
Heat pump/chiller/AC, internal combustion, liquid420 mg/kWh

Fan coil units

Fan coil units have no heat or cold source of their own, so this regulation doesn't set a minimum efficiency or NOx threshold for them — only a requirement to declare rated cooling capacity, rated heating capacity and total electrical power in the technical documentation.

Frequently asked questions

What does Regulation (EU) 2016/2281 cover?

Air heating products up to 1 MW rated heat output, cooling products and high-temperature process chillers up to 2 MW rated cooling capacity, and fan coil units. It excludes products already covered by other ecodesign regulations (local space heaters, portable air conditioners, multi-functional heaters), biomass- or solid-fuel-fired products, cogeneration products, and several other listed exclusions.

Does this tool calculate seasonal efficiency from scratch?

No. The regulation's own text sets the minimum thresholds (Annex II) but delegates the detailed measurement and calculation method to separate, non-public harmonised standards. This tool checks a product's already-declared efficiency and NOx figures against those thresholds — it does not derive efficiency from raw technical data.

Why are there two thresholds, 2018 and 2021?

The regulation phases in two tiers. Tier 1 applied from 1 January 2018 (efficiency) and 26 September 2018 (NOx). Tier 2, the stricter level, applied from 1 January 2021. Since both dates have passed, Tier 2 is the current binding minimum for any product placed on the market today.

Did small B1, C2 and C4 air heaters keep their lower efficiency exception in 2021?

No. Table 1 gave B1 air heaters below 10 kW and C2/C4 air heaters below 15 kW a lower minimum of 68%, against 72% for standard units. Table 2 removes that exception — every non-electric air heater, regardless of size or flue type, must reach 78% from 2021.

Is a fan coil unit required to meet a minimum efficiency under this regulation?

No. Annex II only requires fan coil units to publish declared performance information — there is no minimum efficiency or NOx threshold for this product category.

This checker compares a product's declared values against the minimum thresholds published in Annex II of Regulation (EU) 2016/2281. It does not perform the underlying measurement or derive declared values from raw technical data — that methodology sits in separate harmonised standards referenced by, but not published within, the regulation. It is provided for screening and engineering guidance, not as a conformity assessment. Always verify against the official text before declaring conformity.