Splitter silencer designer

Enter the duct size, splitter count/thickness/length and airflow for a rectangular splitter (baffle) silencer, and get the gap velocity, pressure loss and self-generated flow noise — via VDI 2081 Blatt 1's own correlations, verified against the standard's published worked example.

VDI 2081 Blatt 1, verified Pressure loss + flow noise Free, no sign-up

Silencer data

Inputs only — every result is on the right.

Duty

Duct

Splitters

Acoustic construction

I know my fan's noise in octave bands enter it here to see how much this silencer attenuates it

Octave-band sound power level LW entering the silencer (dB, unweighted) — e.g. from a fan datasheet or the FEI/acoustic calculator elsewhere on this site. Pre-filled with an illustrative example spectrum so you can see the outlet-noise estimate below right away — replace with your own fan's numbers (or clear a field to ignore that band).

Construction & mass

Everything needed to estimate the silencer's built weight — casing shell, curtain cladding sheets, mineral-wool core and end flanges.

Core density affects mass only — neither VDI 2081's pressure-loss/flow-noise formulas nor the ASHRAE insertion-loss estimate take wool density as an input.
Air conditions & display units

Silencer design results

Geometry

Air gap
Duct (face) velocity
Gap velocity
Gap hydraulic diameter
Casing (overall) length

VDI 2081 Blatt 1 — Eq. 42 & 44

Loss coefficient, ζ
Total pressure loss
Self-generated flow noise, LWA Eq. 49

Insertion loss — ASHRAE lined-duct estimate (unverified)

Construction & mass

Casing shell mass
Curtain cladding mass, all splitters
Core (mineral wool) mass, all splitters
Flange mass, both ends
Total silencer mass

Cross-check — general engineering model

Reynolds number
Darcy friction factor
Contraction coefficient Kc
Expansion coefficient Ke
Contraction loss (duct → gaps)
Friction loss (through gaps)
Expansion loss (gaps → duct)
Total (general model)

Link copied — it reopens with these exact inputs.

What this calculates

This implements the actual VDI 2081 Blatt 1 (2001-07) splitter-silencer correlation, Section 7.2.3.2 — an earlier version of this page used a general fluid-mechanics approximation instead, because the formula couldn't be verified against a source at the time. It's now checked against the fully worked numeric example in VDI 2081 Blatt 2 (2005-05), Table 1: for a splitter silencer with s=100 mm, dk=200 mm, L=2.000 m, duct velocity v=4.94 m/s, the standard's own published result is Δpt=145 Pa; this calculator reproduces 145.6 Pa (0.4% difference, within the rounding VDI 2081 itself documents for its tabulated examples) — and the flow-noise result below reproduces the standard's published 52 dB(A) to 0.02 dB.

ζ = a1[s/(s+dk)]b1 + a2[s/(s+dk)]b2 × L/dh VDI 2081-1 Eq. (44) Δpt = ζ × (ρ/2) × v² VDI 2081-1 Eq. (42)

v is the duct (approach) velocity, not the gap velocity — Equation 42's own symbol list defines it that way, and Section 7.2.3.2 doesn't redefine it, so it carries over unchanged. Using the gap velocity here instead was the exact mistake behind the earlier, abandoned reconstruction attempt. Coefficients a1, a2, b1, b2 are tabulated in VDI 2081-1 for exactly three curtain thicknesses (100/200/300 mm); this calculator linearly interpolates between the two bracketing rows for any other thickness you enter, and flags it when your thickness falls outside that 100–300 mm range entirely (the standard doesn't define coefficients beyond it).

The gap width is calculated automatically from duct width, splitter count and splitter thickness, following VDI 2081-1's own Bild 32 arrangement (half-width gaps at each duct wall, full-width gaps between interior splitters): for N splitters of thickness dk, s = W/N − dk — or you can override it directly. The "Technical drawing" panel in the results draws this arrangement to scale — a plan view and a cross-section looking along the flow, both dimensioned — so it's a schematic for checking the arrangement makes sense, not a fabrication/shop drawing. The "3D model" panel below it renders the same geometry with the casing semi-transparent so the splitters (and, if enabled, the end flanges with their bolt positions) are visible — drag to rotate, scroll to zoom. It's a visualization aid, not a CAD model: no gauge-accurate profiles, welds, gaskets or real bolt threads.

Self-generated flow noise

The LWA result is the A-weighted sound power the silencer itself generates from air rushing past the curtains — VDI 2081-1 Equation (49), LWA = 56.6 lg(vgap) − 0.5 lg(Δpt) + 10 lg(S) − 12.7, using the VDI pressure drop above and the duct cross-section area S. This is a different quantity from the silencer's insertion loss (how much it attenuates noise passing through it) — VDI 2081 does not give a formula for that. Section 7.2.2 of the standard is explicit that insertion loss depends on the specific curtain construction and is manufacturer-tested data (its own worked example labels those octave values "Herstellerangaben" — manufacturer's data — not a calculation); typical shapes are shown only as illustrative example curves, not general design equations. VDI 2081-1 gives no formula for it at all, so use your silencer manufacturer's tested octave-band data as the design value.

VDI 2081-1 also gives a polynomial approximation (Eq. 46, 50, 51, using a Strouhal number) for how that total flow noise splits across octave bands. We could not get this specific piece to reproduce the worked example's own numbers with confidence (a consistent ~24% mismatch in the calculated Strouhal numbers we haven't traced to its source), so — consistent with this site's policy of not shipping unverified precision — it isn't implemented here; only the verified total LWA is shown.

Insertion loss — ASHRAE lined-duct estimate (unverified)

Since VDI 2081 gives no formula for insertion loss, the octave-band table below borrows a different, real published source instead: the 2019 ASHRAE Handbook — HVAC Applications, Chapter 49, Tables 17 & 18 — measured insertion loss for a straight rectangular sheet-metal duct lined with 25 mm or 50 mm fiberglass, for five square duct sizes (300–1220 mm) at four tested lengths each. The values were extracted from the source PDF's own text layer, not read off a scan, so they're exact — but everything about how they're used here is an approximation with real limits, disclosed up front rather than hidden:

  • These tables describe a single lined duct, not a multi-curtain silencer. This calculator treats one gap between two curtains as if it were its own small lined duct, matched to the table by P/A (perimeter/area) ratio — the same parameter ASHRAE's own Table 16 organizes duct attenuation by, so it's a reasonable acoustic-engineering analogy, but it is not a citable method for splitter silencers specifically and has no worked example here to check it against.
  • The smallest duct size ASHRAE tabulates (300×300 mm, P/A = 13.3 /m) already has less absorptive surface per unit area than a typical splitter gap (e.g. the VDI 2081 worked example's own gap has P/A = 23.3 /m) — so most real splitter gaps fall outside this table's own tabulated range, requiring extrapolation rather than interpolation. Whenever that happens, the result is flagged explicitly above the table with the nearest reference size used.
  • Length is interpolated between the four tested lengths (2/3/6/12 m) where possible; outside that range it's scaled proportionally with length and capped at 50 dB, matching the cap ASHRAE itself applies.

Treat this table as a rough order-of-magnitude guide for early sizing decisions, not a design value — and definitely not a substitute for a manufacturer's own tested octave-band insertion loss for the actual curtain construction you specify. The table's "Sum" column is a plain arithmetic total of the eight band values, the same shorthand most silencer catalogs quote — it is not an energy- or A-weighted single number.

Outlet noise estimate

If you enter a fan's octave-band inlet sound power spectrum (optional, under "Fan inlet noise spectrum" in the inputs), this calculator estimates what comes out the other end: each band is reduced by the ASHRAE insertion-loss estimate above, the resulting spectrum is A-weighted and logarithmically summed to one overall level, and the silencer's own self-generated flow noise (Eq. 49) is then added to that as an independent broadband source (10 log₁₀[10^(Lattenuated/10) + 10^(Lself-noise/10)]) — it is not distributed across bands, because no verified octave shape exists for it (see above). This chains two approximations end to end (the ASHRAE estimate, and at low velocities the self-noise floor), so use it to compare design options, not as a substitute for a manufacturer's tested acoustic submittal.

Cross-check — general engineering model

Kept alongside the VDI result as an independent sanity check, not because it replaces it: air entering the silencer contracts from the full duct area into the gaps between splitters, runs through the gaps as a straight rectangular duct, then expands back to the full duct area on the way out, using formulas already verified elsewhere on this site — Darcy-Weisbach + Colebrook-White against Moody-chart reference points, and the Borda-Carnot contraction/enlargement coefficients against basic momentum conservation.

Contraction (duct → gaps): Kc = 0.5 × (1 − Agap/Aduct) Friction (through the gaps): Δpf = f × (L/Dh) × ρVgap²/2 Expansion (gaps → duct): Ke = (1 − Agap/Aduct)² Δptotal = KcρVgap²/2 + Δpf + KeρVgap²/2

The two methods agreeing reasonably closely is itself a useful check; a large divergence between them is worth a second look at your inputs.

The pressure-loss and flow-noise figures implement VDI 2081 Blatt 1 (2001-07), Section 7.2.3.2 and 7.2.4.2, verified against the worked example in VDI 2081 Blatt 2 (2005-05). The general-model figures are an independent cross-check using standard fluid-mechanics formulas, not VDI 2081. The insertion-loss octave table is a rough estimate built from 2019 ASHRAE Handbook lined-duct data (Ch. 49, Tables 17-18), applied to a splitter gap by analogy and often extrapolated beyond that data's own tabulated range — it has no worked example to verify it against and should be treated as order-of-magnitude only. Mass figures assume uniform sheet thickness and flat construction — no seams, corner stiffeners, bolts/gaskets or internal frame weight; the optional end flange is a plain flat bar around the casing perimeter, not a real rolled angle-flange profile. The optional outlet noise estimate combines the ASHRAE insertion-loss estimate with the VDI self-noise figure and is only as reliable as those two inputs. Neither VDI 2081 nor this calculator provides a verified insertion-loss design value — that is manufacturer-tested data. Provided for engineering guidance — verify against the manufacturer's tested performance data for critical designs.