Cooling load calculator

Room cooling load from dimensions, design temperatures and envelope U-values — plus solar gain by window orientation and glazing type, internal gains and ventilation. Required cooling capacity in kW, broken down by source.

Transmission + solar + internal + ventilation Shares the Heat Loss envelope tables Free, no sign-up

Room data

Inputs only — every result is on the right.

Room dimensions

Design temperature

Walls

Windows

Doors

Ceiling / roof

Floor

Internal gains & ventilation
Annual energy & cost
Waiting for input

Required cooling capacity for this room.

Transmission gain
Solar gain (windows)
Internal gains
Ventilation gain
Volume
Net wall area
Annual cooling energy
Annual electricity consumption
Annual cooling cost

Link copied — it reopens with these exact inputs.

How to use this calculator

  1. Enter the room dimensions and indoor/outdoor design temperatures.
  2. Pick wall, glazing, door, ceiling and floor constructions, or enter your own U-values.
  3. Enter window area and orientation for solar gain, plus the glazing g-value.
  4. Read the total cooling load, broken down by transmission, solar and internal/ventilation gains.

What this calculates

A room's cooling load is the sum of four physically distinct gains — heat conducted through the envelope, solar radiation through glazing, heat given off by people and equipment inside, and the sensible heat carried in by outdoor air:

Q_transmission = Σ (Ui × Ai × ΔT) for walls, windows, doors, ceiling, floor Q_solar = A_window × g × I_orientation Q_internal = occupants × W_person + A_floor × (W_equip + W_light) Q_ventilation = 0.34 × n × V × ΔT Q_total = Q_transmission + Q_solar + Q_internal + Q_ventilation ΔT = outdoor design temperature minus indoor cooling setpoint, K g = glazing solar heat gain coefficient (g-value / SHGC) I = peak design solar irradiance on the window's orientation, W/m²

This is the same steady-state relationship the Heat Loss / Heating Load calculator uses for transmission and ventilation — this tool loads that calculator's own U-value tables directly rather than duplicating them, so a wall, window, door, ceiling or floor construction picked here means exactly the same U-value it would in the heating calculation. ΔT runs the other way (outdoor warmer than indoor), so heat flows into the room instead of out of it.

Solar gain and orientation

Solar gain is usually the dominant, most variable term in a cooling load — and the one a simple U·A·ΔT calculation misses entirely. It depends on the window area, how much of the incident solar radiation the glazing actually transmits (the g-value — a highly glazed, uncoated window can pass 80%+ of incident solar energy, a solar-control coating as little as 30-35%), and how much radiation hits that facade in the first place, which is why orientation matters. West-facing glazing is the conventional worst case for cooling sizing: afternoon sun arrives at a low angle straight into the glass at the same time the day's outdoor temperature peaks.

Internal gains and ventilation

People, equipment and lighting all add heat that has nowhere to go but into the room — sized here from occupant count and per-m² power densities you can adjust for the actual space. Ventilation uses the same air-heat-capacity relationship as the heating calculator's ventilation term, just with the temperature difference running the other way.

Annual energy and cost

The design-point cooling load above is one worst-case moment — the same degree-day method used by the Heat Loss calculator turns it into an annual estimate, run in the cooling direction: Cooling Degree Days (CDD) sum the whole cooling season's warm weather into one number (a hot day contributes a lot, a mild day little, a winter day nothing), instead of assuming the design-day ΔT holds for the whole year.

Q/K = Q_total / ΔT_design [W/K] Annual cooling energy = Q/K × CDD × 24 / 1000 [kWh/yr] Annual electricity = Annual cooling energy / COP Annual cost = Annual electricity × price

Cooling equipment is almost always electric, so unlike the heating calculator's heat source there's no fuel-unit conversion here — picking a cooling source just sets a typical COP/EER for that equipment type (a basic window AC and a water-cooled chiller can differ by close to 2× in electricity use for the same cooling delivered), and price is always entered per kWh.

This is a simplified steady-state method — useful for a first-pass cooling capacity estimate or comparing design options quickly, not a substitute for a full dynamic cooling load calculation (e.g. CLTD/CLF, RTS or a full building simulation), which accounts for thermal mass and time lag that this single-point calculation does not. Solar irradiance per orientation is a rough, representative "summer design day" figure for a mid-latitude Northern Hemisphere location — not a solar-position, latitude, date or time-of-day calculation. Sensible heat only — no latent (humidity/moisture) load is included; pair this with the Mollier (h-x) calculator if you need the latent side too. The U-value, g-value and cooling-source COP/EER presets are typical/representative values for screening, not a certified figure for any specific product or assembly, and the default electricity price is a round placeholder, not live market data. Cooling degree days is a rough, order-of-magnitude figure — replace it with your own local data if you have it. The degree-day annual estimate assumes the design-point load coefficient stays constant all season (no part-load/free-cooling effects, no occupancy schedule) — treat the annual figures as an order-of-magnitude estimate, not a metered-bill prediction. Provided for engineering guidance — verify against a full calculation for a real design.